Special shear wall detailing is essential for earthquake-resistant reinforced-concrete (RC) buildings. RC shear walls are important elements of the lateral-force-resisting system. They help the structure resist lateral actions such as earthquake forces and control storey displacement. But a shear wall is not just a thick vertical concrete panel. Its dimensions, reinforcement arrangement, boundary regions, openings, coupling beams and foundation connection all need careful attention.

This guide explains the general detailing requirements for special RC structural walls (special shear walls) in Clause 10.1 of IS 13920:2016. It is based on the supplied engineering notes and checked against the published text of the standard and the listed amendments. Amendment No. 1 (September 2017) corrects two expressions in Table 1; Amendment No. 2 (November 2020) updates terminology and other provisions. The worked numbers below are learning examples, not a substitute for project-specific design.

1. What is a special shear wall?

A shear wall, also called a structural wall, is a vertical planar RC member primarily intended to resist lateral effects in its own plane. These effects include axial force, shear force and bending moment. A special shear wall is a structural wall detailed to meet the ductility requirements specified in IS 13920.

In a building, shear walls are commonly arranged around lift cores, staircases or other suitable locations. Their position and continuity matter: a wall should form a clear load path down to its foundation rather than stopping at an unsuitable supporting member.

2. Minimum thickness of special shear walls – Clause 10.1.2

As per Clause 10.1.2, the minimum thickness of a special shear wall shall not be less than:

  • 150 mm for the general case; and
  • 300 mm for buildings with coupled shear walls, in any seismic zone.

The selected thickness must also satisfy the fire-resistance requirements applicable to the building occupancy, as referred to in IS 456. Therefore, meeting the numerical minimum alone does not automatically complete the thickness check.

3. Minimum wall length-to-thickness ratio – Clause 10.1.3

Clause 10.1.3 specifies that the minimum ratio of the horizontal length of the wall to its thickness shall be 4.

Check: Lw / tw ≥ 4

Here, Lw is the horizontal length of the wall and tw is the wall-web thickness. This is a geometric requirement; it should not be confused with the height-to-length ratio used to classify the wall in the next clause.

4. Classification of shear walls – Clause 10.1.4

Special shear walls are classified according to the ratio of overall wall height to horizontal wall length:

Wall typeHeight-to-length ratio
Squat wallhw / Lw < 1
Intermediate wall1 ≤ hw / Lw ≤ 2
Slender wallhw / Lw > 2

In simple terms, a squat wall is relatively short in height compared with its length, while a slender wall has a much greater height relative to its length. This classification is important because the minimum reinforcement provisions vary with wall type.

Special shear wall arrangement showing two reinforced-concrete wall piers connected by coupling beams
Schematic illustration for general understanding; not a BIS standard figure or a construction detail.

5. Effective flange width in flanged walls – Clause 10.1.5

Some structural walls have flanges because a perpendicular wall or return wall is connected to the web. For design of a flanged wall section, the full available flange width cannot automatically be counted as effective.

The effective flange extension beyond the face of the web is limited by the smallest of the following:

  • Actual flange width available;
  • Half the distance to the adjacent structural-wall web; and
  • One-tenth of the total wall height, hw/10.

Use the smaller value when establishing the effective flange width for the section. A plan sketch showing the web, flange and adjacent wall is particularly helpful when applying this clause.

6. Minimum distributed reinforcement – Clause 10.1.6

Special shear walls must have uniformly distributed reinforcement in both the vertical and horizontal directions. The minimum reinforcement area is to be selected from Table 1 of IS 13920, based on whether the wall is squat, intermediate or slender.

Use the applicable row of Table 1 for the wall classification. The minimum ratios shown in the table include horizontal reinforcement, vertical reinforcement in the web, net vertical reinforcement and vertical reinforcement in boundary elements, as applicable. The expressions in Table 1 must be read with Amendment No. 1: for squat walls, the term in the vertical minimum-reinforcement expression is Lw (not tw); for slender walls, the corresponding expression uses ρv,web (not ρh). Do not calculate the required steel from an unamended copy of the table.

Practical point: First classify the wall using hw/Lw. Then identify the web and boundary elements and calculate the required reinforcement using the applicable row and expressions in Table 1. Check the applicable amendments to the standard before final design.

7. When are two curtains of reinforcement required? – Clause 10.1.7

Two curtains (two reinforcement layers, one near each face) are required when either of the following conditions is satisfied:

  • The factored shear-stress demand in the wall exceeds 0.25√fck MPa; or
  • The wall thickness is 200 mm or more.

Each curtain contains bars in both vertical and horizontal directions. Where two layers are provided, all vertical bars must be contained within the horizontal bars; the horizontal bars must form a closed core concrete area using closed loops and cross-ties. The two triggers above are alternatives (OR), so either one is sufficient to require two curtains.

Special shear wall reinforcement detailing with two curtains of vertical and horizontal bars near opposite faces
Illustration of reinforcement curtains; use approved structural drawings for actual bar arrangement.

8. Maximum diameter of longitudinal bars – Clause 10.1.8

The largest diameter of longitudinal steel bars used in any part of the wall shall not exceed one-tenth of the thickness of that part.

Check: φmax ≤ t / 10

For this check, use the thickness of the particular wall part in which the bar is placed. Do not automatically use the overall building-wall dimension if the section thickness changes locally.

9. Maximum spacing of horizontal and vertical reinforcement – Clause 10.1.9

The maximum spacing of vertical or horizontal reinforcement shall not exceed the smallest of these three limits:

  • Lw/5;
  • 3tw; and
  • 450 mm.

Calculate all three limits and use the smallest value. Illustrative check: for Lw = 3,000 mm and tw = 200 mm, the three limits are 600 mm, 600 mm and 450 mm. Therefore, the maximum spacing from Clause 10.1.9 is 450 mm. The design may require closer spacing.

10. Foundation and continuity requirement – Clause 10.1.10

Clause 10.1.10 requires special shear walls to be founded on properly designed foundations. They must not be discontinued so as to rest on beams, columns or inclined members. In practical terms, trace the wall’s force path down to the foundation and design the foundation and its connections for the actions transferred by the wall.

11. Worked geometry and detailing checks (illustrative)

Consider a hypothetical rectangular wall with Lw = 3,000 mm, tw = 200 mm and overall height hw = 9,000 mm. These values are chosen only to demonstrate how the geometric limits are applied; they do not establish that the wall is adequate for any real building.

  • Length-to-thickness: Lw/tw = 3,000/200 = 15, which is greater than the minimum ratio of 4.
  • Wall classification: hw/Lw = 9,000/3,000 = 3, so it falls in the slender-wall category under Clause 10.1.4.
  • Bar diameter limit: t/10 = 200/10 = 20 mm for the 200 mm-thick part being checked.
  • Maximum distributed-bar spacing: min( Lw/5 = 600 mm, 3tw = 600 mm, 450 mm ) = 450 mm.
  • Two curtains: wall thickness is 200 mm, so Clause 10.1.7 requires two curtains regardless of whether the shear-stress trigger is exceeded.

This short check does not cover structural analysis, design shear, axial-flexural interaction, boundary-element design, coupling-beam design, anchorage, development length, construction joints or foundation design. Those checks remain essential.

12. Quick design-review checklist

  • Verify Lw/tw ≥ 4.
  • Confirm that the wall is part of the intended lateral-force-resisting system.
  • Check minimum thickness and fire-resistance requirements.
  • Classify the wall using hw/Lw.
  • Calculate effective flange width where the wall is flanged.
  • Provide the correct minimum vertical and horizontal reinforcement from Table 1.
  • Check whether two curtains are required.
  • Check maximum longitudinal-bar diameter and reinforcement spacing.
  • Confirm proper foundation support and wall continuity.

These topics will help you connect shear-wall detailing with the wider structural-design workflow:

Code reference and important note

Primary reference: IS 13920:2016, Clause 10.1, read with Amendment No. 1 (September 2017) and Amendment No. 2 (November 2020), and relevant provisions of IS 456. The BIS Standard Details page for IS 13920:2016 lists both amendments. In particular, Amendment No. 1 changes two expressions in Table 1; Amendment No. 2 changes terminology in Clauses 3.10 and 3.11 but does not list a change to Clauses 10.1.2–10.1.10. Consult the current licensed BIS text and project requirements before using the provisions for design.

Disclaimer: This is an independent educational article, not an official BIS publication or endorsement. Refer to the latest applicable BIS standards for actual design and construction.

Related Articles: Ductility and R-Values: SMRF vs OMRF | Earthquake-Resistant Building Design | P-Delta Effects in High-Rise Structures